FusionPoD 700 Rack-Scale Server

New Benchmark for Commercial Liquid Cooling Leading Flagship of High-Density Computing Power

Product Introduction

FusionPoD 700 is a rack-scale server with native liquid cooling design as it provides electricity, network and liquid for liquid-cooled servers.The overall architecture design adopts overhead cabling and underfloor water piping, which is more reliable; electricity, network and liquid are equipped with bus and blind mating design, significantly reducing the deployment efforts of cabinet and cables while improving O&M capability toward unmanned O&M. FusionPoD 700 rack-scale server is applicable to be deployed in the data centers that have high requirements on power efficiency and computing power intensity, and is also used in many application scenarios, such as cloud computing, virtualization and HPC when being configured with liquid-cooled servers.

Full Liquid Cooling

Full Liquid Cooling

Unmatched energy efficiency: PUE < 1.1

Mature Ecosystem: cold-plate liquid cooling and eco-friendly materials with zero fluoride

Scale deployment: mature liquid cooling technology, successful commercial deployment and zero liquid leakage incident

Continuous evolution: High-power single chip supports the evolution into high-power CPUs.

Supreme Computing Power

Supreme Computing Power

High computing power intensity: The cabinet supports 36 nodes, equivalent to four racks.

High-density installation: 100% utilization of the rack space

High-density deployment: Integration of L1 and L2 reduces the space of cooling and power distribution equipment, increasing the utilization rate of the equipment room.

Full Monitoring

Full Monitoring

Leakage-proof design: Leakage prevention design in node, cabinet and equipment ensures zero liquid leakage; the three-grade leakage monitoring provides precise alarm within seconds.

Components of high reliability: The liquid cooling system uses high reliable components with over 10 years service life.

System of high reliability: Fault prediction, diagnosis and self-healing capability provide remedial measures and proactive O&M services.

Full Blind Mating

Full Blind Mating

Zero cables and three-bus blind mating: The unique three-bus blind mating capability is supported with zero cables in the rack, supporting automatic O&M and serving as an unmanned data center.

Easy replacement of parts: Memory modules can be replaced without removing the liquid cooling plates.

Rack-scale delivery: The whole cabinet has been installed, tested, and debugged on the production line before being delivered to the customer's equipment room.

Technical Specifications

スペックネーム
パラメータ
FusionPod 700 Cabinet Dimensions (H x W x D)

• Full liquid cooling (including a front door and an RDHx): without casters: 2200 mm x 600 mm x 1400 mm (86.61 in. x 23.62 in. x 55.11 in.), with casters: 2250 mm × 600 mm × 1400 mm (88.58 in. x 23.62 in. x 55.11 in.)

• Board-level liquid cooling (including a front door and a normal back door): without casters: 2200 mm x 600 mm x 1200 mm (86.61 in. x 23.62 in. x 47.24 in.), with casters: 2250 mm × 600 mm × 1200 mm (88.58 in. x 23.62 in. x 47.24 in.)

Technical Specifications

• Available space: 47 U

• Server node: 36 x 1 U server nodes

• Switching node: 4 service switching nodes, 1 out-of-band management switching node, and 1+1 redundancy of service switching nodes

• Cabinet management node: 1 cabinet management module

Power Supply

• Power supply requirement: AC: 4 PSU modules in 2+2 redundancy mode, 380 V/32 A

• PSUs: 11+1 PSUs, 3 kW

Cabinet Power and Heat Dissipation

• System maximum power consumption: 33 kW (backup) and 36 kW (no backup)

• Heat dissipation methods: liquid cooling + air cooling

Environmental Specifications

• Operating temperature: 5°C to 45°C (41°F to 113°F) (ASHRAE Classes A1 to A3 compliant)

• Storage temperature (within three months): –30°C to +60°C (-22°F to +140°F)

• Storage temperature (within six months): –15°C to +45°C (5°F to 113°)

• Storage temperature (within one year): –10°C to +35°C (14°F to 95°F)

• Maximum temperature change rate: 20°C (36°F) per hour, 5°C (9°F) per 15 minutes

Humidity (RH and No Condensing)

• Operating humidity: 8% to 90%

• Storage humidity (within three months): 8% to 85%

• Storage humidity (within six months): 8% to 80%

• Storage humidity (within one year): 20% to 75%

• Maximum change rate: 20% per hour

Altitude

• Operating altitude: no more than 3050 m (10,006.56 ft)

– When the server configuration complies with ASHRAE Class A2 standards and the altitude is above 900 m (2,952.76 ft.), the operating temperature decreases by 1°C (1.8°F) for every increase of 300 m (984.24 ft.)

– When the server configuration complies with ASHRAE Class A3 standards and the altitude is above 900 m (2,952.76 ft.), the operating temperature decreases by 1°C (1.8°F) for every increase of 175 m (574.15 ft)

– When the configuration complies with ASHRAE Class A4 standards and the altitude is above 900 m (2,952.76 ft.), the operating temperature decreases by 1°C (1.8°F) for every increase of 125 m (410.10 ft)

Installation

• Installation dimensions: cabinet projection area: 600 mm x 1350 mm (23.62 in. x 53.15 in.); reserve at least 1.2 m (3.94 ft) space for maintenance in front of and behind the cabinet

• Package size (W x H x D): 980 mm x 2405 mm x 1310 mm (38.58 in. x 94.69 in. x 51.47 in.) (except the front door and the back door)

• Fully loaded weight: 1200 kg

• Cabinet package weight: 34.8 kg

• Equipment room: no less than 1000 kg/m²

• Equipment room floor height: no less than 600 mm (23.62 in.)

• Manifold pipe installation port: 1-inch flange quick port

• RDHx pipe installation port: 1-inch flange quick port

Cooling

• Manifold water supply requirement: pH value: ≥ 6.5; glycol-concentration: 25% ± 5% (volume concentration); total microorganism count: < 105 CFU/mL

Turbidity: no visible impurities in the filter net

• Manifold water supply temperature: 5℃ to 45℃ (41°F to 113°F)

• Manifold recommended water supply temperature: 30℃ (86°F)

• Manifold water supply flow: 32 LPM

• Manifold water supply maximum pressure: 350 kPa

• Manifold supply and return water pressure difference: 35 kPa at 25% glycol solution

もっと 少ない

Technical Support

View All

Documentation

Documents about introduction, installation and deployment etc

Viewiew

Software Download

Download drivers and firmware of products

View

Case Library

A collection of excellent practices, troubleshooting, and O&M skills

View